Description:
Provides a seamless information flow between Modbus and PROFINET networks; GT200-PN-RS can connect multiple devices with RS-232/RS422/RS-485 interface to PROFINET network.
 
Technical Specification:
 
  1. Protocol conversion between PROFINET and Modbus.
2. Supports standard PROFINET I/O RT protocol.
3. PROFINET: supports up to 32 slots, input/output data buffer is up to 1024 bytes (the length uses can use is limited to specific PLC and PDU size of communication module), the length of input/output bytes can be set by STEP7.
4. The protocol type serial ports support: Modbus master, Modbus slave, simple-defined protocol.
5. With 3 serial ports, supports RS-232 or RS-485 electrical interface, serial III can also support RS-422:
Operation mode: half duplex;
Baud rate: 300, 600, 1200, 2400, 9600, 19200, 38400, 57600 and 115200bps;
Check bit: none, odd, even, mark and space optional;
Stop bits: 1 bit, 2 bits.
6. Modbus master:
Function code: 01H, 02H, 03H, 04H, 05H, 06H, 0FH and 10H;
Format: RTU and ASCII;
Function: Cycle output, forbidden output and change of value output of write command;
Each master can configure up to 48 Modbus commands.
7. Modbus slave:
Function code: 03H, 04H, 06H and 10H;
Format: RTU and ASCII.
8. Built-in electrostatic protection: 15 KV ESD; Communication interface isolation: 3KV.
9. Power supply: 24VDC (11V-30V), 90mA (24VDC).
10. Operating Temp.: -4