GT200-3HT-MT gateway can connect HART slave devices to Modbus TCP network.
 
Technical Specification:
 
  1. Supports three HART channel and each channel can connect 13 HART devices when using internal resistor and 15 HART devices when using an external resistor (250Ω).
2. Acts as a primary master or secondary master on HART network, supports burst mode, long frame format and all HART commands.
3. HART interface supports single-point mode and multi-point mode.
4. Automatic baud rate detection on Ethernet (10/100M).
5. As Modbus TCP server, supports up to 36 Modbus TCP clients connections, Modbus TCP can support 512 command request.
6. Easy configuration with free SST-HE-CFG software tool.
7. Operating Temp.:-40ºF to 158ºF(-40ºC to 70ºC),Rel. Humidity: 5%-95% RH non-condensing.
8. Dimension(W*H*D):40mm*125mm*110mm(1.6in*4.9in*4.5in).
9. Mounting:DIN Rail Mounting(35mm).