首页>Modbus Series>Modbus/EtherNet IP>GT100-EI-RS
  GT100-EI-RS
   
 
GT100-EI-RS
Description:
GT100-EI-RS can connect multiple Modbus slave devices to the EtherNet / IP network.
 
Technical Specification:
 
  1. Independent between EtherNet/IP network and Modbus network.
2. Ethernet 10/100M self-adaptive.
3. IP address conflict detection.
4. Support ODVA standard EtherNet/IP communication protocol.
5. Serial is RS485 or RS232 interface, half duplex, baud rate: 1200,2400, 4800, 9600, 19200,38400, 57600, 115200bps optional, check bit: None, odd, even, mark and space optional; 1 or 2 bit stop bit optional.
6. Act as Modbus Master at Modbus side, support function code 01H, 02H, 03H, 04H, 05H, 06H, 0FH, 10H, support at most 48 Modbus command, Modbus function 03H, 04H, 06H, 10H support byte exchange function, convenient for resolving the format problem of big-endian and small endian between two network data.
7. Under universal mode, support frame timeout, frame length and delimiter control mode, automatic sending function.
8. 1KV galvanic isolated on two RS485 or RS232 interface.
9. EtherNet/IP maximum input/output bytes:
Maximum input bytes: 492 bytes (Under universal mode, maximum input bytes is 256 bytes)
Maximum output bytes: 492 bytes (Under universal mode, maximum output bytes is 256 bytes)
10. Power supply: 24VDC (11V-30V), 90mA (24VDC).
11. Operating Temp.: -40ºF to 140ºF (-40ºC to 60ºC), Rel. Humidity: 5%-95%, non-condensing.
12. Dimension (W*H*D): 0.98in*3.94in*3.54in (25mm*100mm*90mm).
13. Mounting: DIN Rail Mounting (35mm).